RE-2X(St)H + PIMF / TIMF Cl

Construction

Conductor : Bare or tinned annealed circular stranded copper wires complying with IEC 60228
Mica Tape : Helical applied fire resistant tape
Insulation : XLPE in accordance with EN 50290-2-29
Tape : Polyester tape
Wire : Tinned copper drain wire
Tape : Metal coated polyester tape
Tape : Polyester tape
Wire : Tinned copper drain wire
Tape : Metal coated polyester tape
Outer Jacket : HFFR compound in accordance with EN 50290-2-27

Technical Features

Operating Temperature : -40/90 °C
Rated Voltage : 300/500 V

Design Guideline : IEC 50288-7
Halogen Free Properties : IEC 60754-1 & IEC 60754-2
Low Smoke Emission : IEC 61034-1 & IEC 61034-2
Flame Propagation : IEC 60332-1, IEC 60332-3-22 CAT.A
Fire Endurance : IEC 60331-21
Oil Resistant : EN 50290-2-22 (Optional)

Application

Fixed installation for power, control and lighting in safe areas, emergency and critical onshore or offshore
applications where requirement for mechanical stress.

Technical Data

RE-2X(St)H+PIMF Cl TECHNICAL DATA SHEET

Max. Current Carrying Capacity
Outer Diameter  Max. Conductor  Conductor Temperature at 90 °C
Item Cross- section  Weight (approx.) (approx.) Resistance at 20  °C Ambient Temperature at 45  °C
(mm²) ( kg/km ) ( mm ) (ohm/km) (A) ( Air )
1. 1 x 2 x 0,75 89 8,6 24,5 13
2. 2 x 2 x 0,75 184 12,8 24,5 11
3. 4 x 2 x 0,75 236 14,8 24,5 7
4. 7 x 2 x 0,75 353 17,8 24,5 7
5. 12 x 2 x 0,75 577 23,8 24,5 7
6. 19 x 2 x 0,75 843 28 24,5 6
7. 37 x 2 x 0,75 1547 38,2 24,5 5
8. 1 x 2 x 1 98 9 18,1 15
9. 2 x 2 x 1 205 13,4 18,1 13
10. 4 x 2 x 1 275 15,8 18,1 9
11. 7 x 2 x 1 402 18,8 18,1 9
12. 12 x 2 x 1 661 25,1 18,1 9
13. 19 x 2 x 1 971 29,6 18,1 8
14. 37 x 2 x 1 1791 40,4 18,1 6
15. 1 x 2 x 1,5 114 9,6 12,1 20
16. 2 x 2 x 1,5 243 14,5 12,1 16
17. 4 x 2 x 1,5 332 17,1 12,1 11
18. 7 x 2 x 1,5 505 20,6 12,1 11
19. 12 x 2 x 1,5 832 27,5 12,1 11
20. 19 x 2 x 1,5 1230 32,5 12,1 10
21. 37 x 2 x 1,5 2278 44,4 12,1 8
22. 1 x 2 x 2,5 145 10,8 7,41 26
23. 2 x 2 x 2,5 332 16,9 7,41 16
24. 4 x 2 x 2,5 455 20 7,41 11
25. 7 x 2 x 2,5 699 24,1 7,41 11
26. 12 x 2 x 2,5 1155 32,3 7,41 11
27. 19 x 2 x 2,5 1739 38,4 7,41 10
28. 37 x 2 x 2,5 3229 52,5 7,41 8

 

RE-2X(St)H+TIMF Cl TECHNICAL DATA SHEET

Max. Current Carrying Capacity
Outer Diameter  Max. Conductor  Conductor Temperature at 90 °C
Item Cross- section  Weight (approx.) (approx.) Resistance at 20  °C Ambient Temperature at 45  °C
(mm²) ( kg/km ) ( mm ) (ohm/km) (A) ( Air )
1. 1 x 3 x 0,75 90 8 24,5 10
2. 2 x 3 x 0,75 184 12,3 24,5 8
3. 4 x 3 x 0,75 250 14,2 24,5 7
4. 7 x 3 x 0,75 381 17,1 24,5 7
5. 12 x 3 x 0,75 615 22,5 24,5 6
6. 19 x 3 x 0,75 911 26,6 24,5 5
7. 37 x 3 x 0,75 1690 36,3 24,5 5
8. 1 x 3 x 1 101 8,4 18,1 12
9. 2 x 3 x 1 211 13 18,1 10
10. 4 x 3 x 1 291 15,1 18,1 8
11. 7 x 3 x 1 447 18,2 18,1 8
12. 12 x 3 x 1 738 24,3 18,1 7
13. 19 x 3 x 1 1097 28,6 18,1 6
14. 37 x 3 x 1 2040 39 18,1 6
15. 1 x 3 x 1,5 122 9,1 18,1 16
16. 2 x 3 x 1,5 259 14,3 12,1 12
17. 4 x 3 x 1,5 376 16,8 12,1 11
18. 7 x 3 x 1,5 584 20,2 12,1 11
19. 12 x 3 x 1,5 968 27 12,1 9
20. 19 x 3 x 1,5 1447 31,8 12,1 8
21. 37 x 3 x 1,5 2703 43,5 12,1 8
22. 1 x 3 x 2,5 163 10,4 12,1 22
23. 2 x 3 x 2,5 367 17 7,41 17
24. 4 x 3 x 2,5 537 20 7,41 15
25. 7 x 3 x 2,5 844 24,2 7,41 15
26. 12 x 3 x 2,5 1403 32,4 7,41 13
27. 19 x 3 x 2,5 2131 38,5 7,41 11
28. 37 x 3 x 2,5 3992 52,7 7,41 11