Aluminium Wire Armoured Power Cables U-2XOHFFRAL / 2XR(A)H FR 0,6/1kV CU/MGT/XLPE/HFFR-F/AWA/LS0H IEC 60502-1
- Construction
- Technical Features
- Technical Data
Conductor : Annealed circular stranded or compact copper wires complying with IEC 60228 Class 2
Mica Tape : Helical applied fire resistant tape
Insulation : Cross-linked polyethylene, XLPE in accordance with IEC 60502-1
Bedding : Halogen-free compound
Armour : Aluminium wire in accordance with IEC 60502-1
Tape : Polyester or aluminium wrapping tape
Outer Jacket : Halogen-free compound, ST8 in accordance with IEC 60502-1
Operating Temperature : -40/90 ˚C
Rated Voltage : 0,6/1 kV
Design Guide : IEC 60502-1
Halogen Free Properties : IEC 60754-1 & IEC 60754-2
Low Smoke Emission : IEC 61034-1 & IEC 61034-2
Flame Retardancy : IEC 60332-1
Flame Propagation : EC 60332-3-22 Cat. A
Fire Endurance : EC 60331-21
Cold Bend : CSA C22.2 No. 0.3-09 ( -40°C )
Cold Impact : CSA C22.2 No. 0.3-09 ( -35°C )
Application : Fixed installation for power, control and lighting in safe areas, emergency, critical oil and gas onshore and industrial plants.
Item | Type | Cross- section (mm²) |
Weight (approx.) (kg/km) | Outer Diameter (approx.) (mm) |
Max. Conductor Resistance at 20 °C (ohm/km) |
Max. Current Carrying Capacity Conductor Temperature at 90 °C Ambient Temperature at 45 °C(A) ( Air ) |
||
1. | U-2XOHFFRAL- 2XR(A)H FR | 2 | x | 2,5 | 318 | 15,2 | 7,41 | 27 |
2. | 2 | x | 10 | 645 | 20,1 | 1,83 | 60 | |
3. | 2 | x | 25 | 1280 | 27,6 | 0,727 | 108 | |
4. | 3 | x | 2,5 | 399 | 16,7 | 7,41 | 22 | |
5. | 3 | x | 10 | 757 | 21,1 | 1,83 | 50 | |
6. | 3 | x | 25 | 1544 | 29,2 | 0,727 | 88 | |
7. | 4 | x | 2,5 | 459 | 17,8 | 7,41 | 22 | |
8. | 4 | x | 10 | 988 | 23,9 | 1,83 | 50 | |