U-2XOHFFRC ; 2XCH-FR

Copper Wire Armoured Power Cables
U-2XOHFFRC / 2XCH FR 0,6/1kV
CU/MGT/XLPE/HFFR-F/CUW/LS0H
IEC 60502-1

Construction

Conductor : Annealed circular stranded or compact copper wires complying with IEC 60228 Class 2
Mica Tape : Helical applied fire resistant tape
Insulation : Cross-linked polyethylene, XLPE in accordance with IEC 60502-1
Bedding : Halogen-free compound
Armour : Copper wire and copper tape
Outer Jacket : Halogen-free compound, ST8 in accordance with IEC 60502-1

Technical Features

Operating Temperature : -40/90 ˚C
Rated Voltage : 0,6/1 kV

Design Guide : IEC 60502-1
Halogen Free Properties : IEC 60754-1 & IEC 60754-2
Low Smoke Emission : IEC 61034-1 & IEC 61034-2
Flame Retardancy : IEC 60332-1
Flame Propagation : EC 60332-3-22 Cat. A
Fire Endurance : EC 60331-21
Cold Bend : CSA C22.2 No. 0.3-09 ( -40°C )
Cold Impact : CSA C22.2 No. 0.3-09 ( -35°C )

Technical Data

 

Item Type Cross- section (mm²) Weight (approx.) (kg/km) Outer Diameter
(approx.) (mm)
Max. Conductor
Resistance at 20  °C (ohm/km)
Max. Current Carrying Capacity Conductor Temperature at 90 °C Ambient Temperature at 45  °C(A) ( Air )
1 2×2,5/2,5 312 15,3 7,41 27
2 2×10/10 608 19,3 1,83 60
3 2×25/16 1147 25,5 0,727 108
4 3×2,5/2,5 348 15,9 7,41 22
5 3×10/10 709 20,3 1,83 50
6 3×25/16 1374 26,9 0,727 88
7 4×2,5/2,5 399 17 7,41 22
8 4×10/10 846 21,8 1,83 50
9 4×25/16 1692 29,5 0,727 88