Collective Screened Fire Resistant, Halogen Free, Flame Retardant, Low Smoke
- Construction
- Application Standards
- Technical Data
Construction
Conductor : Tinned stranded copper in accordance with IEC 60228 CL2, CL5
Insulation : Ethylene Propylene Rubber (EPR), GP4 in accordance with BS 7655-1.2
Tape : Polyester tape
Wire : Tinned copper drain wire
Tape : Metal coated polyester tape
Outer Jacket : Halogen free extruded compound, SW4 in accordance with BS 7655-2.6
Application Standards
Max. Operating Temperature : 90 °C
Rated Voltage : 250 V
Design Guidelines : BS 6883
Halogen Free Properties : IEC 60754-1 & IEC 60754-2
Low Smoke Emission Flame : IEC 61034-1 & IEC 61034-2
Low Smoke Emission Flame Retardancy : IEC 60332-1
Flame Propagation : IEC 60332-3-22 Cat. A
Technical Data
Item | Type | Cross- section (mm²) | Weight (approx.) ( kg/km ) | Outer Diameter (approx.) ( mm ) | MCDR at 20 °C ( Ω/km ) | Inductance (approx.) (mH/km) | Capacitance (approx.) (nF/km) | L/R ratio (μH/Ω) | Rated Voltage (V) | MCCC CT at 90 °C AT at 45 °C (A) |
1. | U-8RW4T (C) | 3 x 2 x 0,75 | 213 | 12,3 | 24,8 | 0,74 | 92 | 30 | 250 | 8 |
2. | 7 x 2 x 0,75 | 442 | 16,7 | 24,8 | 0,74 | 92 | 30 | 7 | ||
3. | 12 x 2 x 0,75 | 720 | 22 | 24,8 | 0,74 | 92 | 30 | 7 | ||
4. | 20 x 2 x 0,75 | 1150 | 27,5 | 24,8 | 0,74 | 92 | 30 | 5 | ||
5. | 27 x 2 x 0,75 | 1516 | 31,5 | 24,8 | 0,74 | 92 | 30 | 5 | ||
6. | 37 x 2 x 0,75 | 2038 | 35,6 | 24,8 | 0,74 | 92 | 30 | 5 | ||
7. | 3 x 2 x 1 | 245 | 13 | 18,2 | 0,75 | 107 | 41 | 10 | ||
8. | 7 x 2 x 1 | 520 | 17,8 | 18,2 | 0,75 | 107 | 41 | 9 | ||
9. | 12 x 2 x 1 | 834 | 23,2 | 18,2 | 0,75 | 107 | 41 | 9 | ||
10. | 20 x 2 x 1 | 1335 | 19,1 | 18,2 | 0,75 | 107 | 41 | 6 | ||
11. | 27 x 2 x 1 | 1781 | 33,5 | 18,2 | 0,75 | 107 | 41 | 6 | ||
12. | 37 x 2 x 1 | 2394 | 37,9 | 18,2 | 0,75 | 107 | 41 | 6 | ||
13. | 3 x 3 x 0,75 | 272 | 14,3 | 24,8 | 0,74 | 92 | 30 | 7 | ||
14. | 7 x 3 x 0,75 | 573 | 19,6 | 24,8 | 0,74 | 92 | 30 | 7 | ||
15. | 12 x 3 x 0,75 | 870 | 24,9 | 24,8 | 0,74 | 92 | 30 | 5 | ||
16. | 3 x 3 x 1 | 321 | 15,3 | 18,2 | 0,75 | 107 | 41 | 9 | ||
17. | 7 x 3 x 1 | 683 | 21 | 18,2 | 0,75 | 107 | 41 | 9 | ||
18. | 12 x 3 x 1 | 1015 | 26,3 | 18,2 | 0,75 | 107 | 41 | 6 |