U-2VOVC ; YCY

Copper Wire Armoured Power Cables
U-2VOVC / YCY 0,6/1kV
CU/PVC/PVC-F/CUW/PVC
IEC 60502-1

Construction

Conductor : Annealed circular stranded or compact copper wires complying with IEC 60228 Class 2
Insulation : PVC/A in accordance with IEC 60502-1
Bedding : PVC compound
Wire : Bare annealed copper wire
Tape : Copper wrapping tape
Outer Jacket : PVC compound ST1 in accordance with IEC 60502-1

Technical Features

Operating Temperature : -15/70 ˚C
Rated Voltage : 0,6/1 kV

Design Guide : IEC 60502-1
Flame Retardancy : IEC 60332-1

Technical Data

 

Item Type Cross- section
(mm²)
Weight (approx.) (kg/km) Outer Diameter
(approx.) (mm)
Max. Conductor
Resistance at 20  °C (ohm/km)
Max. Current Carrying Capacity Conductor Temperature at 90 °C
Ambient Temperature at 45  °C(A) ( Air )
1. YCY 2 x 2,5/2,5 282 14,5 7,41 19
2. 2 x 10/10 623 19,3 1,83 42
3. 2 x 25/16 1156 25 0,727 76
4. 3 x 2,5/2,5 320 15 7,41 15
5. 3 x 10/10 730 20,2 1,83 35
6. 3 x 25/16 1404 26,3 0,727 62
7. 4 x 2,5/2,5 368 16 7,41 15
8. 4 x 10/10 871 21,8 1,83 35
9. 4 x 25/16 1729 28,7 0,727 62