U-2VOVC ; YCY
- Home
- Oil and Gas Cables
- U-2VOVC ; YCY
Copper Wire Armoured Power Cables U-2VOVC / YCY 0,6/1kV CU/PVC/PVC-F/CUW/PVC IEC 60502-1
- Construction
- Technical Features
- Technical Data
Construction
Conductor : Annealed circular stranded or compact copper wires complying with IEC 60228 Class 2
Insulation : PVC/A in accordance with IEC 60502-1
Bedding : PVC compound
Wire : Bare annealed copper wire
Tape : Copper wrapping tape
Outer Jacket : PVC compound ST1 in accordance with IEC 60502-1
Technical Features
Operating Temperature : -15/70 ˚C
Rated Voltage : 0,6/1 kV
Design Guide : IEC 60502-1
Flame Retardancy : IEC 60332-1
Technical Data
Item | Type | Cross- section (mm²) |
Weight (approx.) (kg/km) | Outer Diameter (approx.) (mm) |
Max. Conductor Resistance at 20 °C (ohm/km) |
Max. Current Carrying Capacity Conductor Temperature at 90 °C Ambient Temperature at 45 °C(A) ( Air ) |
||
1. | YCY | 2 | x | 2,5/2,5 | 282 | 14,5 | 7,41 | 19 |
2. | 2 | x | 10/10 | 623 | 19,3 | 1,83 | 42 | |
3. | 2 | x | 25/16 | 1156 | 25 | 0,727 | 76 | |
4. | 3 | x | 2,5/2,5 | 320 | 15 | 7,41 | 15 | |
5. | 3 | x | 10/10 | 730 | 20,2 | 1,83 | 35 | |
6. | 3 | x | 25/16 | 1404 | 26,3 | 0,727 | 62 | |
7. | 4 | x | 2,5/2,5 | 368 | 16 | 7,41 | 15 | |
8. | 4 | x | 10/10 | 871 | 21,8 | 1,83 | 35 | |
9. | 4 | x | 25/16 | 1729 | 28,7 | 0,727 | 62 |