U-2XVOVC ; 2XCY

Copper Wire Armoured Power Cable
U-2XVOVC / 2XCY 0,6/1kV
CU/XLPE/PVC-F/CUW/PVC
IEC 60502-1

Technical Features

Operating Temperature : -15/90 ˚C
Rated Voltage : 0,6/1 kV

Design Guide : IEC 60502-1
Flame Retardancy : IEC 60332-1
Flame Propagation : IEC 60332-3-24 Cat. C

Technical Data

 

Item Type Cross- section
(mm²)
Weight (approx.) (kg/km) Outer Diameter
(approx.) (mm)
Max. Conductor
Resistance at 20  °C (ohm/km)
Max. Current Carrying Capacity Conductor Temperature at 90 °C
Ambient Temperature at 45  °C(A) ( Air )
1. 2XCY 2 x 2,5/2,5 264 14,1 7,41 27
2. 2 x 10/10 564 18,1 1,83 60
3. 2 x 25/16 1072 23,8 0,727 108
4. 3 x 2,5/2,5 298 14,6 7,41 22
5. 3 x 10/10 660 18,9 1,83 50
6. 3 x 25/16 1302 25 0,727 88
7. 4 x 2,5/2,5 340 15,5 7,41 22
8. 4 x 10/10 784 20,3 1,83 50
9. 4 x 25/16 1587 27,1 0,727 88